Fire Resistant Wires & Cables

BE offers Low Voltage Fire Resistant Wires and Cables, in accordance with International (IEC) and British (BS) standards.

FR wires & cables are used in a wide range of electrical applications like emergency systems, stand-by power supplies and elevators in subway substations, airports, public locations, hotels and hospitals.

BE is the first accredited company in KSA by BASEC and LPCB for Fire Resistant wires and cables. All tests of FR wires and cables are carried out in accordance with IEC 60502-1, BS 7846, BS 7211 and BS 6387 CAT CWZ in its own laboratories accredited by A2LA ISO/IEC 17025:2005.

  Download Catalogue

  Send RFQ

FSB WIRE | CU/MICA/LSOH-XL | 450/750V | BS Standard

Specification:

  • Designation Type H07Z-R and H07Z-K BS 7211. Flame Retardant to IEC 60332-1 Vertical Flame Propagation Test. Products tested at internationally reputable labs, LPCB, BASEC & bsi.

Conductor:

  • Soft annealed copper according to BS EN 60228, Class 2 stranded and Class 5 flexible conductor wrapped with mica tapes.

Insulation:

  • Halogen free, low smoke cross-linked material (LS0H-XL) of Type EI 5 to EN 50363-5 90 °C. Colors are available upon request.

LPCB & BASEC Approvals:

  • BS 6387 (CWZ) test under flame temperature 950 °C for 3 hour
  • IEC 60331-21
  • BS EN 50200(PH-120)

Special Requirements (upon request):

  • Different packing options are available.

Low Voltage Fire Resistant Cables | IEC & BS Standards

Bahra Fire Resistant Cable Types:

Single & Multi core cable unarmored


Multi core cable armored BS 7846 - F2


Single core cable armored


Multi core cable armored BS 7846 - F120

Specification:

  • Electrical low voltage cables complying with IEC 60502-1 BS 7846. Our products tested at internationally reputable labs,LPCB, BASEC & bsi. All cable are Flame Retardant to IEC 60332-3.24 Category C Flame Propagation Test, Oil esistance and Sunlight & UV Resistant. Fire resistant test as per BS 6387 (CWZ) 950 °C for 3 hour.

Conductor:

  • High conductivity soft annealed copper according to BS EN 60228, Class 1, Class 2 stranded and Class 5 flexible conductor wrapped with mica tapes. Conductor can be offered with round, round compacted and sectored shape.

Insulation:

  • Cross-linked polyethylene (XLPE) with Maximum service temperature 90ºC.

Armoring (upon request):

  • Aluminum Wire Armored “AWA” for single core cable.
  • Galvanized steel wire “SWA” for multi core cable.

Outer Sheathing:

  • Low Smoke & Fume Zero Halogen (LS0H)

Special Requirements (upon request):

  • High flame propagation tests: IEC 60332-3.23 Category B - IEC 60332-3.22 Category A
  • Fire performance: F120 - F2 - IEC 60331 - BS 6387 (CWZ)
  • Water resistance
  • Anti-termite resistant
  • Shield type
  • Polyvinyl chloride (PVC ST2) outer sheath
  • Special color for insulation and outer sheath
  • Different packing options are available

Watch video for Fire Resistance lab testing